Beskrivning av upphandlingen
The thermal rating is 95 MW fuel input. District heating temperature to the plant around 60°C and from the plant 115°C. Design data for mechanical design is Water side: 16 Bar(g)/120°C. The mechanical design needs to be selected such that the equipment is fitted in the available space in the existing building.
The dimensions of the available space are: With: 9,6 meters, Height: 14,6 meters, Length: 15,7 meters.
The boiler and flue gas fans shall be located within the available space.
The boiler will be installed during the first half of 2018.