General This prequalification is for a turnkey contract that consists modernization and conversion of burners in four existing boilers, P11, P12, P13, P14, at Värtaverket, Stockholm. The boilers shall be able to run on heavy oil (EO5), Bio oil (MFA) and Pitch oil (Boiler P14). As general, the following applies: — The delivery shall comply with the applicable regulations and policies. The necessary certificates, CE declarations and test certificate shall be included in the scope of delivery. — Delivery terms NLM 10E with modifications by Fortum Heat Scandinavia. Background, Steam automized Boiler P11 and Boiler P12 are placed in heating plant 1 (Värmeverk 1) in Värtaverket, Stockholm. They are two EO5 fired hot water boilers from Götaverken built in 1969. The boilers are each equipped with 4 Babcock & Wilcox YEL(steam atomized) burners with a capacity at 3200kg/h per burner. Boiler P13 and Boiler P14 are placed in heating plant 2 (Värmeverk 2) are two EO5 fired boile.
Sista ansökningsdag
Tidsfristen för mottagande av anbud var 2015-05-18.
Upphandlingen offentliggjordes den 2015-04-17.
Meddelande om upphandling (2015-04-17) Objekt Upphandlingens omfattning
Titel: Installation av ånggeneratorer, turbiner, kompressorer och brännare
Kvantitet eller omfattning: According to description above.
Meddelandeinformation
Originalspråk: engelska 🗣️
Dokumenttyp: Meddelande om upphandling
Kontraktets art: Tjänster
Reglering: Europeiska unionen – inom ramen för avtalet om offentlig upphandling
Gemensam upphandlingsterminologi (CPV)
Kod: Installation av ånggeneratorer, turbiner, kompressorer och brännare📦
Förfarande
Förfarandetyp: Förhandlat förfarande
Anbudstyp: Anbud på alla delar
Kriterier för tilldelning
Det ekonomiskt mest fördelaktiga
Upphandlande myndighet Identitet
Land: Sverige 🇸🇪
Upphandlande myndighet (typ): Allmännyttigt företag
Upphandlande myndighet (namn): Fortum Värme samägt med Stockholms Stad
Postadress: Lidingövägen 115
Postnummer: 115 77
Postort: Stockholm
Kontakt
E-post: per.kohler@partners.fortum.com📧
Referens Datum
Avsändningsdatum: 2015-04-17 📅
Sista anbudsdag: 2015-05-18 📅
Publiceringsdatum: 2015-04-22 📅
Identifierare
Meddelandenummer: 2015/S 078-138953
EUT-S-nummer: 78
Ytterligare information
Boilers from Maskinverken built in 1972. Boiler P14 has been rebuilt to operate with Pitch Oil or EO5.
Boiler P13 is equipped with 6 Hamworthy HPD (steam atomized) burners with capacity 2 840 kg/h per burner.
Boiler P14 has 3 newer Hamworthy-LNO ( low-nox, steam atomized) with the capacity at 4 170 kg/h (for pitch oil) and 3 835 kg/h for EO5 per burner, and three Hamworthy HPD burners. The three LNO-burners and one HPD burner are rebuilt to be fired with Pitch Oil. The combustion air system is supplemented with a ROFA-system.
Scope
The turnkey contract includes:
— For boiler P11 and P12 in Värmeverk 1 modernization and conversion of the burners and related systems to be able to run on Bio Oil (MFA) and EO5. The work will include the redevelopment of the burners or as alternative new burners, a new oil system with piping and a redundant oil skid that shall be able to supply both the boilers during full operation with EO5 or Bio Oil (MFA).
Mechanical, electrical and Burner management system (BMS) installation.
— For boiler P13 and P14 in Värmeverk 2 modernization and conversion of the burners and related systems to be able to run on Bio Oil (MFA), EO5. Boiler P14 shall also run on Pitch Oil. The work will include the redevelopment of the burners or as alternative new burners, a new oil system with piping and redundant oil skid that shall be able to supply both the boilers during full operation with EO5 or Bio Oil (MFA), for Pitch Oil the existing oil skid will be reused. The existing ROFA-system shall be included in the new BMS.
Mechanical, electrical and Burner management system (BMS) installation.
The BMS shall be tight integrated with the new DCS this work shall be included in the scope of the work.
The work includes all the necessary equipment within the delivery boundaries to meet the functional and performance requirements of the upcoming request.
Emission (to air) requirements for the contract
Boiler
P11-P13
SO2 400 mg/m3 N dry gas
NOx 400 mg/m3 N dry gas
Dust 20 mg/m3 N dry gas
P14
SO2 200 mg/N m3 N dry gas
NOx 150 mg/m3 N dry gas
Dust 20 mg/m3 N dry gas
Visma Commerce notice: http://www.opic.com/notice.asp?req=dissrfkc
Boilers from Maskinverken built in 1972. Boiler P14 has been rebuilt to operate with Pitch Oil or EO5.
Boiler P13 is equipped with 6 Hamworthy HPD (steam atomized) burners with capacity 2 840 kg/h per burner.
Boiler P14 has 3 newer Hamworthy-LNO ( low-nox, steam atomized) with the capacity at 4 170 kg/h (for pitch oil) and 3 835 kg/h for EO5 per burner, and three Hamworthy HPD burners. The three LNO-burners and one HPD burner are rebuilt to be fired with Pitch Oil. The combustion air system is supplemented with a ROFA-system.
Scope
The turnkey contract includes:
— For boiler P11 and P12 in Värmeverk 1 modernization and conversion of the burners and related systems to be able to run on Bio Oil (MFA) and EO5. The work will include the redevelopment of the burners or as alternative new burners, a new oil system with piping and a redundant oil skid that shall be able to supply both the boilers during full operation with EO5 or Bio Oil (MFA).
Mechanical, electrical and Burner management system (BMS) installation.
— For boiler P13 and P14 in Värmeverk 2 modernization and conversion of the burners and related systems to be able to run on Bio Oil (MFA), EO5. Boiler P14 shall also run on Pitch Oil. The work will include the redevelopment of the burners or as alternative new burners, a new oil system with piping and redundant oil skid that shall be able to supply both the boilers during full operation with EO5 or Bio Oil (MFA), for Pitch Oil the existing oil skid will be reused. The existing ROFA-system shall be included in the new BMS.
Mechanical, electrical and Burner management system (BMS) installation.
The BMS shall be tight integrated with the new DCS this work shall be included in the scope of the work.
The work includes all the necessary equipment within the delivery boundaries to meet the functional and performance requirements of the upcoming request.
Objekt Upphandlingens omfattning
Tjänstekategori: 1
Kort beskrivning:
General
This prequalification is for a turnkey contract that consists modernization and conversion of burners in four existing boilers, P11, P12, P13, P14, at Värtaverket, Stockholm.
The boilers shall be able to run on heavy oil (EO5), Bio oil (MFA) and Pitch oil (Boiler P14).
As general, the following applies:
— The delivery shall comply with the applicable regulations and policies. The necessary certificates, CE declarations and test certificate shall be included in the scope of delivery.
— Delivery terms NLM 10E with modifications by Fortum Heat Scandinavia.
Background, Steam automized
Boiler P11 and Boiler P12 are placed in heating plant 1 (Värmeverk 1) in Värtaverket, Stockholm. They are two EO5 fired hot water boilers from Götaverken built in 1969. The boilers are each equipped with 4 Babcock & Wilcox YEL(steam atomized) burners with a capacity at 3200kg/h per burner.
Boiler P11 and Boiler P12 are placed in heating plant 1 (Värmeverk 1) in Värtaverket, Stockholm. They are two EO5 fired hot water boilers from Götaverken built in 1969. The boilers are each equipped with 4 Babcock & Wilcox YEL(steam atomized) burners with a capacity at 3200kg/h per burner.
Boiler P13 and Boiler P14 are placed in heating plant 2 (Värmeverk 2) are two EO5 fired boile.
Varaktighet: 23 månader
Referensnummer: 25297
Plats för genomförandet
Huvudort eller plats för utförandet: Stockholm.
Juridisk, ekonomisk, finansiell och teknisk information Villkor för deltagande
Behörighet att utöva yrkesverksamheten:
The buyer will invite a maximum of 10 suppliers to participate the tendering process.
Ekonomisk och finansiell ställning: At least 5 employees and a turnover of more than 1 000 000 EUR annually.
Teknisk och yrkesmässig förmåga:
The supplier shall be able to perform on-site services within 8 hour upon request.
Show at least 3 references on deliveries with similarly size of burners that comply with exhaust emission requirements.
Kontraktets fullgörande
Depositioner och garantier som krävs: N/A.
De viktigaste finansieringsvillkoren och betalningsarrangemangen och/eller hänvisning till de relevanta bestämmelserna om dem: N/A.
Juridisk form för den grupp av ekonomiska aktörer som ska tilldelas kontraktet: N/A.
Andra särskilda villkor: According to description.
Förfarande
Information om personer som har rätt att närvara och öppningsförfarande: